Lantech 72W Dual Output Power Supply with DIN Rail Clip

Part Number : AD1072-48F

    £ 44.99 £ 44.99 44.99 GBP

    £ 44.99

    + VAT

    This combination does not exist.

    Add to Cart
    AD1072-48F

    AD1072-48F Power series is rigid and compact design for space saving and industrial applications. It supports power ready signal and ring diode circuit for redundant application as well as over-voltage, over-load and short circuit protection.



    • Output voltage: 24V, 48V
    • Operating Temperature: -20°C - 50°C
    • High Power Density
    • DIN rail / Wall bracket mounting solution
    • Overload protection
    • Short circuit protection
    • Convection cooled
    • 1 year warranty


    General

    Switching Frequency70k Hz
    Isolation Voltage - Input-Output
    3000 VAC/4242 VDC
    Isolation Voltage - Input-FG
    1500 VAC/2121 VDC
    Isolation Voltage - Output-FG
    500 VAC/710 VDC
    Isolation Resistance
    100MQ when Input-Output @500VDC
    Operating Temperature
    -40°C ~ +50°C ambient
    Derating
    2.5% per degree from 50°C to 70°C
    Storage Temperature
    -40°C ~ +85°C
    Relative Humidity
    5%-95% RH, Non-condensing
    Temperature Coefficient
    +0.04% of output voltage per °C
    MTBF
    60,000hrs Min. Per MIL-HDBK-217F, 25°C GB
    Altitude During Operation
    2000m
    Installation position
    Vertical
    Vibration
    Random vibration, 10-500Hz, 3 axise


    Input

    Input Voltage
    100-240VAC/120-370VDC
    Input Frequency
    47-63 Hz

    Inrush Current 
    (cold start)

    22A/115VAC
    44A/230VAC

    Rated Input Current
    1.5A Max., Vi=100-240VAC
    Leakage Current
    Input-output 0.25mA, Input-FG 3.5mA


    Output

    Output Voltage accuracy
    +-1%
    Minimum Load
    0%
    Line Regulation
    +-1%, measuring from low line to high line at rated load.
    Load Regulation
    +-1%, measuring from 20% to 100% of rated load at 230VAC input.
    Voltage Trim Range
    +-10% (Min.)
    Rated Continuous Loading
    2.5A@24VDC
    Hold Up Time
    20ms Min., Full load@230VAC.
    Turn On Time
    1200ms
    Rise Time
    10ms
    Fall Time
    30ms
    Transient Response Recovery Time
    2mS, Load change 50% to 100%
    Transient Response Voltage Deviation
    5%, Load change 50% to 100%
    Efficiency
    See model list, measuring at rated load and 230VAC input.
    Ripple and Noise
    See model list, measuring by using a 0.1uF/630V metalize capacitor and a 47uF electrolytic capacitor parallel on the test point, at rated load and 230VAC inpu


    Protection

    Input Fuse
    2A/250V
    Internal Surge Load Protection
    Varistor, IEC 61000-4-5
    Degree of Protection
    IP20
    Short Circuit Protection
    Autorecovery
    Over Voltage Protection
    Autorecovery
    Rated Over Load Protection
    160-180%
    Overload protection
    Power limited

    1 x Output Power Supply


    1 x DIN Rail Clip